Demand response of district heating using model predictive control to prevent the draught risk of cold window in an office building

No Thumbnail Available
Journal Title
Journal ISSN
Volume Title
A1 Alkuperäisartikkeli tieteellisessä aikakauslehdessä
Date
2021-01
Major/Subject
Mcode
Degree programme
Language
en
Pages
Series
Journal of Building Engineering
Abstract
Demand response of district heating provides one tool for decreasing cost and emissions in the whole energy system. However, when seeking cost savings and emission reductions, it is also important to consider thermal comfort. Thus, the overall and local thermal comfort of occupants were investigated during the experimental study while applying the demand response of space heating. Thermal manikin measurements were used to reveal the draught risk of convection flow caused by cold windows. Results show that when the surface temperature of windows was below 15°C while the thermostat valves of the radiators were closed, the draught risk became unacceptable. The main objective of the simulation with the developed predictive control algorithm (MPC) was to show how much the minimization of draught risk by limiting minimum window surface temperature to 15°C during decentralized demand response control effects heating energy cost-saving potential. Results show the maximum annual district heat energy cost saving by demand response control without minimization of draught risk is 4.8% and 3.8% with energy-efficient (U=1.0 W/m2K) or poor (U = 2.6 W/m2K) windows respectively, but the draught risk is high with the poor windows. The minimization of draught risk has an insignificant effect on the cost-saving with the energy-efficient windows, but the cost-saving was reduced to 2.3% and draught risk significantly decreased with the poor windows. Thus, it is necessary to use the window temperature restriction with demand response control of radiator heating to prevent the draught risk of cold poorly insulated windows within the thermal comfort range.
Description
| openaire: EC/H2020/856602/EU//FINEST TWINS
Keywords
demand response, thermal comfort, model predictive control, thermal manikin, optimization
Other note
Citation
Wu , Y , Mäki , A , Jokisalo , J , Kosonen , R , Kilpeläinen , S , Salo , S , Liu , H & Li , B 2021 , ' Demand response of district heating using model predictive control to prevent the draught risk of cold window in an office building ' , Journal of Building Engineering , vol. 33 , 101855 . https://doi.org/10.1016/j.jobe.2020.101855