Measured performance of exhaust air heat pumps in Finnish apartment buildings

Loading...
Thumbnail Image

Access rights

openAccess
publishedVersion

URL

Journal Title

Journal ISSN

Volume Title

A4 Artikkeli konferenssijulkaisussa

Date

2021-03-29

Major/Subject

Mcode

Degree programme

Language

en

Pages

7

Series

E3S Web of Conferences, Volume 246

Abstract

The energy efficiency of existing apartment buildings is playing an important role in energy and climate targets. In Finland, mechanical exhaust ventilation system is commonly used in older apartment buildings. Hence, there could be an energy saving potential by an exhaust air heat pump system (EAHP). In this work two cases have been studied. Buildings were built in 1960's and 1970's and in renovation equipped with hybrid heating system: district heating and exhaust air heat pump system. Two years measurement data, 2018 and 2019, was collected to evaluate the performance of exhaust air heat pump systems. According to measurement data the monthly coefficient of performance (COP) was calculated as well as seasonal coefficient of performance (SCOP) was defined. The monthly COP values varied from 3,1 to 4,6 and SCOP values were about 3,7. Heating energy cost savings were 23-31 %. Energy performance class before and after EAHP installation was calculated. If at least 50 % of heating energy consumption was covered by EAHP then also energy performance class was improved.

Description

| openaire: EC/H2020/856602/EU//FINEST TWINS Publisher Copyright: © The Authors, published by EDP Sciences, 2021. Copyright: Copyright 2021 Elsevier B.V., All rights reserved.

Keywords

Other note

Citation

Pylsy, P & Kurnitski, J 2021, ' Measured performance of exhaust air heat pumps in Finnish apartment buildings ', E3S Web of Conferences, vol. 246, 06001 . https://doi.org/10.1051/e3sconf/202124606001