Supercapacitor Implementation on an Uninterruptible Power Supply

No Thumbnail Available

URL

Journal Title

Journal ISSN

Volume Title

Sähkötekniikan korkeakoulu | Master's thesis

Date

2014-05-05

Department

Major/Subject

Elektroniikka ja sovellukset

Mcode

S3007

Degree programme

EST - Elektroniikka ja sähkötekniikka

Language

en

Pages

61

Series

Abstract

Superkondensatorernas kapacitans har stigit, vilket möjliggör deras användning inom områden som vanligen präglas av ackumulator-energireserver. Superkondensatorer tål bättre laddningar och urladdningar i förhållande till ackumulatorer. I detta diplomarbete undersöks möjligheten att använda superkondensatorer som huvudenergireserv för avbrottsfria kraftförsörjningssystem (UPS). Olika UPS topologier och egenskaper presenteras, efter vilket superkondensatorerna presenteras. De nödvändiga förändringarna för att omvandla en vanlig ackumulator-UPS till en superkondensator-UPS presenteras och superkondensatorns funktion som energireserv simuleras. Bara UPS:ens mjukvaran modifieras, inga förändringar i hårdvaran görs. Implementationen testas och veriferas fungera rätt. Problem, som till exempel den ömsesidiga induktanssens påverkan på batteri-omvandlaren undersöks och en lösning presenteras. Målet att omvandla en ackumulator-UPS till en superkondensator-UPS fylls och UPS:sen klarar av att driva sin fulla specifierade belastning i 12 sekunder.

The capacity of supercapacitors has risen to levels which makes it feasible to use them as energy reserves in applications that are dominated by battery-type energy reserves to improve cycling charge and discharge lifetime. This thesis explores the possibility to use supercapacitors as the main backup energy reserve for uninterruptible power supplies. Different types of UPS topologies and characteristics are reviewed followed by an overview of the supercapacitor. The modifications needed to convert a VRLA-battery UPS to a supercapacitor UPS are discussed followed by supercapacitor behavior simulation as an energy reserve. The UPS is only firmware modified, no hardware modifications were made. The implementation details are discussed and are then tested to verify the operation. Issues as, for example, mutual inductance affecting the battery converter is explored and a solution developed. The goal of converting a battery UPS to a supercapactor UPS is achieved and the UPS is able to provide 12 seconds of backup run time with supercapacitors as its main backup energy source.

Description

Supervisor

Ovaska, Seppo

Thesis advisor

Koehler, Stephan

Keywords

supercapacitor, ultracapacitor, battery, energy reserve, UPS, superkondensator, ultrakondensator, batteri, energireserv

Other note

Citation