Effect of sprinklers on the patient's survival probability in hospital room fires
Loading...
Access rights
openAccess
URL
Journal Title
Journal ISSN
Volume Title
A1 Alkuperäisartikkeli tieteellisessä aikakauslehdessä
This publication is imported from Aalto University research portal.
View publication in the Research portal (opens in new window)
View/Open full text file from the Research portal (opens in new window)
Other link related to publication (opens in new window)
View publication in the Research portal (opens in new window)
View/Open full text file from the Research portal (opens in new window)
Other link related to publication (opens in new window)
Date
2021-03
Department
Major/Subject
Mcode
Degree programme
Language
en
Pages
11
Series
Fire Safety Journal, Volume 120
Abstract
The effectiveness of sprinklers in protecting a patient in a hospital room fire was investigated by performing 26 sprinklered and four free-burn experiments in real hospital rooms equipped with water-based automatic suppression system. Three different fire loads were used: UL 1626 corner test fire and two different textile fires. The measurements included temperatures, pipe pressure, and concentrations of about 20 different gas compounds. Based on the measurement results, we calculated the Fractional Effective Dose (FED) and Fractional Irritant Concentration (FIC) –values, and estimated the likelihood of incapacitation as a function of time. The results showed that sprinklers maintained temperatures at low level and reduced toxicity, mainly through fire development control. In UL1626 and large textile fires, sprinklers decreased the patient's incapacitation probability from 0.9 or above to the level of 0.4. In small textile fires, the difference between the incapacitation probabilities of sprinklered fires and free-burns was less than the measurement uncertainty. FED results were sensitive to the calculation method due to the different treatment of NOx –gases.Description
Keywords
FED, Sprinklers, Suppression, Toxicity
Other note
Citation
Hostikka, S, Veikkanen, E, Hakkarainen, T, Kajolinna, T & Kling, T 2021, ' Effect of sprinklers on the patient's survival probability in hospital room fires ', Fire Safety Journal, vol. 120, 103092 . https://doi.org/10.1016/j.firesaf.2020.103092