Critical discussion on the challenges of integrating heat pumps in hydronic systems in existing buildings
No Thumbnail Available
Access rights
embargoedAccess
URL
Journal Title
Journal ISSN
Volume Title
A2 Katsausartikkeli tieteellisessä aikakauslehdessä
This publication is imported from Aalto University research portal.
View publication in the Research portal (opens in new window)
Other link related to publication (opens in new window)
View publication in the Research portal (opens in new window)
Other link related to publication (opens in new window)
Date
2025-07-01
Major/Subject
Mcode
Degree programme
Language
en
Pages
23
Series
Energy, Volume 326
Abstract
The integration of heat pumps into existing buildings is one option to exploit carbon neutral heat and cool sources. Today, this is in line with planned electrification and paths to achieve nearly zero energy buildings by using renewable energy sources. However, the implementation process is more complex compared to new buildings. Moreover, there is no comprehensive study that depicts and critically discusses the main challenges associated with integrating heat pumps into existing buildings from a very practical point of view. This article presents the main technical and economic challenges related to the application of heat pumps in existing building stock based on critical literature review and discussion. Among others, especially, procedures involving the reduction of the supply temperature of the heating medium, the selection of the bivalent point, heat storage, and buffer tanks of heat pumps were discussed. Several best practices for the design and control of the heat pumps in existing buildings along with a discussion of benefits and limitations (technical, economic, operational) of the analyzed systems are provided. Key findings are: (i) it was indicated that the heat pumps in existing buildings can be applied as a heat source for the entire building, part or single room and for different purposes (space heating and/or DHW and/or cooling), (ii) minimisation of the supply temperature is always desirable, with the limit for DHW being 58 °C, and ultimately the control should be adapted to the building or replaced by forecast-based control, (iii) coverage of heat demand by heat pumps should reach 70–90 % of peak demand at nominal outdoor air conditions and be determined on the basis of the analysis of initial and running costs, (iv) from the point of view of reducing the demand for primary energy self-consumption of electricity from PV should be maximised. Finally, future research and development directions are suggested.Description
Keywords
carbon neutral buildings, carfbon neutrality, energy efficiciency, energy renovation, existing building, heat pump, Carbon neutral buildings, Carbon neutrality, Heat pump, Existing building, Energy renovation, Energy efficiency
Other note
Citation
Cholewa, T, Bejan, A-S, Miara, M, Schauer, C, Kosonen, R, Borodinecs, A, Bogdanovics, R, Amanowicz, Ł, Vering, C, Siuta-Olcha, A, Skwarczynski, M A, Kropp, M, Kurnitski, J, Lungu, C, Croitoru, C, Afshari, A, d'Ambrosio Alfano, F R, Müller, D, Nastase, I, Todorovic, M & Sekret, R 2025, ' Critical discussion on the challenges of integrating heat pumps in hydronic systems in existing buildings ', Energy, vol. 326, 136158 . https://doi.org/10.1016/j.energy.2025.136158