Dynamic performance of displacement ventilation in a lecture hall

Loading...
Thumbnail Image

Access rights

openAccess
acceptedVersion

URL

Journal Title

Journal ISSN

Volume Title

A4 Artikkeli konferenssijulkaisussa

Major/Subject

Mcode

Degree programme

Language

en

Pages

11

Series

pp. 234-244

Abstract

An accurate temperature gradient calculation is essential for displacement ventilation (DV) system design, since it directly relates to the calculation of the required supply air flow rate. Inaccurate temperature prediction can cause the poor thermal comfort and wrong sizing of the ventilation and cooling systems. Several simplified nodal models were developed and implemented in the various building simulation software to estimate the temperature stratification in rooms with DV. Recent studies reveal that the multi-nodal models provide the most accurate temperature gradient prediction. However, the majority of dynamic calculation methods assumes either complete mixing of zone air or linearised temperature gradient. The present study introduces the dynamic temperature gradient model for DV and investigates the effect of thermal mass on the temperature stratification. The model was validated with the experimental results of a lecture room with displacement ventilation. The room air temperature measurements were conducted during three weeks at 20 different heights. The supply air temperature and occupancy rate were recorded during each scheduled lecture. The developed dynamic nodal model is able to accurately calculate the air temperatures in occupied zone. The effect of the thermal mass and changing heat loads on the indoor air temperature stratification is analysed for the lecture room with DV.

Description

Other note

Citation

Lastovets, N, Siren, K, Kosonen, R, Jokisalo, J & Kilpeläinen, S 2019, 'Dynamic performance of displacement ventilation in a lecture hall', Paper presented at Annual AIVC Conference, Ghent, Belgium, 15/10/2019 - 16/10/2019 pp. 234-244.