Effects of ventilation improvement on measured and perceived indoor air quality in a school building with a hybrid ventilation system

Loading...
Thumbnail Image

Access rights

openAccess

URL

Journal Title

Journal ISSN

Volume Title

A1 Alkuperäisartikkeli tieteellisessä aikakauslehdessä

Date

2018-07-05

Major/Subject

Mcode

Degree programme

Language

en

Pages

18

Series

INTERNATIONAL JOURNAL OF ENVIRONMENTAL RESEARCH AND PUBLIC HEALTH, Volume 15, issue 7

Abstract

Ventilation system design and operation may significantly affect indoor air quality (IAQ). The aims of this case study were to investigate the functionality of a supply air fan-assisted hybrid ventilation system in a newly built school building with reported IAQ problems and to determine the effects of ventilation improvement on measured and perceived IAQ. The ventilation system function was researched simultaneously with IAQ measurements, with an analysis of total volatile organic compounds (TVOC), single volatile organic compounds (VOCs), and indoor mycobiota, and with questionnaires about perceived IAQ. At the baseline, an operational error of the ventilation system was found, which prevented the air from coming into the classrooms, except for short periods of high carbon dioxide (CO2 ) concentrations. After the ventilation operation was improved, a significant change in indoor mycobiota was found; the dominant, opportunistic human pathogenic species Trichoderma citrinoviride found in settled dust in the classroom before the improvement was no longer detected. In addition, the concentrations of CO2, TVOC, and some single VOCs, especially toluene and decamethylcyclopentasiloxane, decreased. The analysis of the questionnaire results indicated that the perceptions of unpleasant odors and stuffy air decreased, although a statistically significant improvement in perceived IAQ was not observed. The results provided evidence that the properly controlled hybrid ventilation system operating in mechanical supply mode provided adequate ventilation and was effective in decreasing the concentrations of some indoor-generated pollutants. With simple ventilation adjustments, microbiological exposure from building structures might be prevented.

Description

Keywords

Hybrid ventilation, Indoor air quality, Indoor air questionnaire, Mycobiota, School building, Trichoderma citrinoviride, Ventilation

Other note

Citation

Vornanen-Winqvist, C, Salonen, H, Järvi, K, Andersson, M A, Mikkola, R, Marik, T, Kredics, L & Kurnitski, J 2018, ' Effects of ventilation improvement on measured and perceived indoor air quality in a school building with a hybrid ventilation system ', International Journal of Environmental Research and Public Health, vol. 15, no. 7, 1414 . https://doi.org/10.3390/ijerph15071414