An Experimental Study on the Efficacy of Local Exhaust Systems for the Mitigation of Exhaled Contaminants in a Meeting Room

Loading...
Thumbnail Image

Access rights

openAccess

URL

Journal Title

Journal ISSN

Volume Title

A1 Alkuperäisartikkeli tieteellisessä aikakauslehdessä

Date

2024-05-01

Major/Subject

Mcode

Degree programme

Language

en

Pages

17

Series

Buildings, Volume 14, issue 5

Abstract

In industrial applications, local exhaust systems have been used extensively for capturing and confining contaminants at their source. The present study investigates the efficacy of these systems in mitigating the spread of exhaled pollutants by combining them with mixing and displacement ventilation. Experiments were conducted in a simulated meeting room with six closely situated workstations, featuring five exposed persons (simulated with heated dummies) and one infected person (simulated with a breathing manikin). Six overhead local exhaust units, merged with panels, corresponding to workstations, were installed using a lowered false ceiling. Additionally, a table plenum setting for air inlets was introduced to enhance displacement ventilation effectiveness along with local exhaust systems. Results from 16 experimental cases are presented, using the local air quality index and ventilation effectiveness in the breathing zone. The local exhaust system improved the local air quality at the measuring locations closest to the infector in almost all test scenarios. The improvement, particularly significant with displacement ventilation, marked a maximum 35% increase in the local air quality index adjacent to the infector and 25% in the entire breathing zone of the tested meeting room. Moreover, the table plenum settings, coupled with displacement ventilation, further enhanced conditions in the breathing zone. Under the specific conditions of this investigation, the number of operational local exhausts had a marginal impact on mixing ventilation but a significant one on displacement ventilation tests. The efficacy of local exhaust systems was also influenced by the levels of heat gains present in the room. Overall, the study aims to contribute to ongoing efforts to identify sustainable solutions to mitigate indoor airborne diseases with a combination of supply and local exhaust units.

Description

Keywords

airborne transmission, contaminant removal, local exhaust, meeting room, respiratory pollutants

Other note

Citation

Ejaz, F, Kilpeläinen, S, Mustakallio, P, Zhao, W & Kosonen, R 2024, ' An Experimental Study on the Efficacy of Local Exhaust Systems for the Mitigation of Exhaled Contaminants in a Meeting Room ', Buildings, vol. 14, no. 5, 1272 . https://doi.org/10.3390/buildings14051272